Молимо вас користите овај идентификатор за цитирање или овај линк до ове ставке: https://open.uns.ac.rs/handle/123456789/12068
Назив: Fault analysis of string based inverters PV plant with the reference to harmonics resonance effect
Аутори: Dumnić, Boris 
Liivik E.
Popadić, Bane 
Milićević, Dragan 
Katić, Vladimir 
Blaabjerg F.
Датум издавања: 1-сеп-2019
Часопис: 2019 21st European Conference on Power Electronics and Applications, EPE 2019 ECCE Europe
Сажетак: © 2019 EPE Association. The paper analyzes a photovoltaic (PV) power system plant based on string inverters operating in parallel and it specifically analyzes the faults experienced in the plant system. A fault classification and a root-cause analysis oriented to be used for reliability improvement are done based on field experience acquired through long-term operation and maintenance activities in a 536 kW PV power plant. The harmonic resonance effect, that can appear with significant negative consequences in multiple string inverters based PV systems, is carefully considered as being one of the most frequent reasons for operation faults. Practical reliability improvement suggestions are also given.